500 kVA Pad Dipasang Transformer-13,2 / 0,48 kV|USA 2025
Kapasitas: 500 kVA
Tegangan: 13200GrdY/7620-480V
Fitur: DOE 2016

500 kVA pad mounted transformer-nyediakake daya sing aman, resik, lan efisien kanthi standar kinerja DOE 2016
01 Umum
1.1 Latar mburi Proyek
Proyèk iki nyakup pasokan trafo distribusi 500 kVA telung-pad fase-dipasang, dirancang kanggo sistem 60 Hz kanthi voltase utami 13,2 kV GrdY / 7620 V lan voltase sekunder 480 V. Trafo kasebut nduweni fitur pendinginan ONAN (Oil Natural Air Natural), pendinginan lan konfigurasi feed ngarep sing aman, lan konfigurasi feed loop sing aman. Dibangun kanthi klompok vektor YNd1 lan duwe impedansi 5,75%.
Diprodhuksi tundhuk karo standar efisiensi energi DOE 2016, trafo sing dipasang pad 500 kva menehi kinerja dhuwur kanthi mundhut energi sing sithik -5,75 kW tanpa beban lan mundhut 0,65 kW ing kapasitas sing dirating.
Trafo sing dipasang 500 kVA 13,2 kV / 480 V telung -fase pad-iki becik kanggo distribusi voltase -sedheng nganti -rendhek ing wilayah kutha lan pinggiran kutha. Aplikasi khas kalebu:
• Komunitas omah, nyuplai daya kanggo lampu, HVAC, lan peralatan rumah tangga
• Kompleks komersial kayata kantor, supermarket, lan taman toko
• Fasilitas industri ènthèng, nguwasani peralatan lan mesin ukuran cilik nganti -sedheng
• Institusi kaya sekolah lan rumah sakit mbutuhake daya sing dipercaya lan aman
• Sistem distribusi Underground, digunakake ing jaringan feed loop kanggo linuwih lan safety
Desaine pad-dipasang, loop-, lan mati-desain ngarep ndadekake cocok kanggo instalasi tingkat ruangan utawa lemah- sing penting papan, safety, lan aksesibilitas.
1.2 Spesifikasi Teknis
500kVA telung phase pad dipasang spesifikasi trafo lan data sheet
|
Dikirim menyang
Amerika
|
|
taun
2025
|
|
Jinis
Trafo pemasangan pad telung fase
|
|
Standar
IEEE Std C57.12.34-2022
|
|
Daya Rated
500KVA
|
|
Frekuensi
60 HZ
|
|
Feed
Loop
|
|
Ngarep
mati
|
|
fase
telu
|
|
Tipe Cooling
ONAN
|
|
Tegangan utami
13,2 kV
|
|
Tegangan Sekunder
0,48 kV
|
|
Kelompok Vektor
YNd1
|
|
Bahan Winding
alumunium
|
|
Impedansi
5.75%
|
|
Efisiensi lan kerugian
DOE 2016
|
|
Tutul Ganti
NLTC
|
|
Ngetuk Range
±2*2.5%
|
|
Ora Mundhut Load
5.75 W
|
|
Ing Load Loss
0.65 W
|
|
Aksesoris
Konfigurasi standar
|
1.3 Gambar
500 kva pad dipasang spesifikasi trafo lan lembar data
![]() |
![]() |
02 Produksi
2.1 Inti
Lima-desain inti sikil njamin jalur fluks magnetik sing imbang kanggo kabeh telung fase. Malah ing nol-arus urutan-kayata sing disebabake dening siji-garis-menyang-lemah lemah-utawa nalika kondisi muatan sing ora seimbang, fluks magnet bisa mili lancar liwat loro sikil njaba. Iki nyuda reluctance magnetik, nyuda kenaikan suhu, lan nyuda geter.
Struktur inti iki utamané mupangati kanggo transformer grup vektor YNd, amarga menehi dalan sing cetha kanggo fluks urutan nol -nalika netral sisih voltase dhuwur-disambungake dhuwur-netral, saéngga nambah stabilitas listrik lan linuwih sistem.
2.2 Penggulungan

Penggulungan voltase dhuwur -nggunakke sambungan lintang (Y) kanthi jumlah giliran sing luwih dhuwur kanggo njamin distribusi voltase seragam lan kinerja insulasi sing apik. Penggulungan tegangan -sedheng disambungake ing konfigurasi delta (D), dirancang kanggo arus sing luwih dhuwur lan giliran sing luwih sithik, biasane nggunakake struktur gulung foil kanggo nambah kekuatan mekanik lan daya dukung arus-iki.
Klompok vektor YNd1 umume digunakake ing sistem tenaga Amerika Utara sing mbutuhake isolasi voltase dhuwur- lan{2}}sedheng, mitigasi harmonik, lan kemampuan grounding.
2.3 Tank
Trafo sing dipasang pad 500 kva iki nduweni tangki minyak baja ringan sing disegel kanthi tutup bolt, nyedhiyakake integritas mekanik sing kuwat lan tahan karat. Iki ngliwati tes bocor tekanan saben IEC 60076-1 kanggo njamin kinerja kenceng lenga.
Seperangkat radiator bergelombang dipasang ing mburi, segel-dilas menyang tank kanggo nambah hawa adhem alami nalika njaga operasi bebas bocor-. Desain kompak iki ndhukung kinerja termal sing stabil lan -reliabilitas jangka panjang ing aplikasi energi resik.

2.4 Rapat pungkasan

Sajrone perakitan pungkasan, komponen utama dipasang kanggo mesthekake operasi sing aman lan dipercaya saka trafo sing dipasang pad 500 kVA-.
Sisih dhuwur -tegangan kalebu enem bushing terisolasi 200A sing bisa dipisahake lan bushing netral H0 khusus kanggo grounding. Sisih voltase -rendhek nduweni rong bushing jinis resin-cast spade-karo enem-terminal bolongan kanggo sambungan kabel sing aman.
Piranti proteksi kalebu telung sekring bayonet lan telung -sekring watesan (CLF) saiki kanggo isolasi fault, bebarengan karo telung arrester lonjakan utama kanggo njaga saka acara overvoltage.
Pad grounding kanthi sambungan siji-bolongan diwenehake ing sisih HV lan LV kanggo ndhukung grounding situs sing aman. Kabeh komponen dipasang kanthi tepat kanggo nyukupi standar utilitas lan kinerja.
03 Testing

Tes Rutin lan Standar Tes
1. Pengukuran Resistansi Isolasi: IEEE C57.12.90-2021 Klausa 10.11
2. Tes rasio: IEEE C57.12.90-2021 Klausa 7; IEEE C57.12.00-2021 Klausa 9.1
3. Uji Hubungan Fase: IEEE C57.12.90-2021 Klausa 6
4. Pengukuran Resistance: IEEE C57.12.90-2021 Klausa 5
5. Ora Ana Mundhut lan Ora Ana Beban Saiki: IEEE C57.12.90-2021 Klausul 8,IEEE C57.12.00-2021 Klausul 9.3
6. Tes Tahan Tegangan Induksi: IEEE C57.12.90-2021 Klausa 10.7
7. Load Losses, Impedansi Voltage lan efficiency: IEEE C57.12.90-2021 Klausa 9; IEEE C57.12.00-2021 Klausa 9.2
8. Tes Tegangan Terapan: IEEE C57.12.90-2021 Klausa 10.6
9. Uji Bocor Kanthi Tekanan Kanggo Cairan-Transformer Tercemplung: IEC60076-1
Asil Tes
|
Ora. |
Item Tes |
Unit |
Nilai Penerimaan |
Nilai sing diukur |
Kesimpulan |
|
1 |
Pengukuran Resistance |
% |
Tingkat unbalance resistance maksimum |
2.29 |
Lulus |
|
2 |
Tes rasio |
% |
Penyimpangan rasio voltase ing tapping utama: Kurang saka utawa padha karo 0,5% Simbol sambungan: YNd1 |
-0.05% ~ -0.03% |
Lulus |
|
3 |
Uji hubungan fase-. |
/ |
YNd1 |
YNd1 |
Lulus |
|
4 |
Ora ana -mundhut lan arus eksitasi |
/ |
I0 :: nyedhiyakake nilai sing diukur |
0.27% |
Lulus |
|
P0: nyedhiyakake nilai sing diukur (t: 20 derajat) |
0,577 kW |
||||
|
toleransi kanggo ora mundhut beban yaiku +10% |
/ |
||||
|
5 |
Load losses voltase impedansi lan efficiency |
/ |
t:85 toleransi kanggo impedansi yaiku ± 7,5% toleransi kanggo mundhut beban total yaiku +6% |
/ |
Lulus |
|
Z%: nilai sing diukur |
5.67% |
||||
|
Pk: nilai sing diukur |
4,032 kW |
||||
|
Pt: nilai diukur |
4,609 kW |
||||
|
Efisiensi ora kurang saka 99,35% |
99.41% |
||||
|
6 |
Tes Tegangan Terapan |
kV |
HV: 34kV 60s LV: 10kV 60s |
Ora ana ambruk voltase test |
Lulus |
|
7 |
Tes Induksi Tegangan Tahan |
kV |
Tegangan sing ditrapake (KV):2Ur |
Ora ana ambruk voltase test |
Lulus |
|
Duration(s):48 |
|||||
|
Frekuensi (HZ): 150 |
|||||
|
8 |
Tes Kebocoran |
kPa |
Tekanan: 20 kPA |
Ora bocor lan ora karusakan |
Lulus |
|
Duration: 12h |
|||||
|
9 |
Pengukuran Resistance Insulation |
GΩ |
HV-LV menyang Ground : |
21.5 |
/ |
|
LV-HV menyang Ground: |
51.6 |
||||
|
HV&LV menyang Ground |
21.2 |
04 Pengepakan lan Pengiriman
4.1 Pengemasan

4.2 Pangiriman
Sadurunge mbukak, ngukur ukuran lan bobot trafo, lan rencana rute sing ngindhari watesan dhuwur, jembar, lan bobot. Gunakake -amben cilik utawa truk khusus kanthi kapasitas sing cukup.
Selarasake pusat gravitasi trafo karo kendaraan. Gunakake baja saluran lan cara pengikat sing tepat kanggo ngamanake pangkalan menyang truk, yen diijini. Ngamanake trafo karo slings utawa chain liwat bolongan transportasi ditetepake, Nyingkiri komponen pecah kayata radiator lan bushings. Kunci komponen internal lan segel kabeh lawang.
Tansah kacepetan Kurang saka utawa padha karo 60 km / jam lan ngiringake Kurang saka utawa padha karo 15 derajat nalika transportasi. Ngindhari gerakan dadakan lan getaran sing kuat. Nemtokake kawalan kanggo mriksa naleni lan mungkasi transportasi ing cuaca abot.
Nalika ngangkat, njaga sudhut tali Kurang saka utawa padha karo 60 derajat. Gunakake bar spreader yen perlu. Tansah angkat munggah, lan kanggo unit tanpa lugs ndhuwur, nggunakake rod ngangkat ngisor.
05 Situs lan Ringkesan
Trafo distribusi 500 kVA, 13,2 kV / 480 V telung fase-dipasang- iki nduweni grup vektor YNd1, menehi kemampuan isolasi lan grounding voltase medium sing apik banget -nganti{7}}disesuaiake kanggo sistem tenaga Amerika Utara. Lima-desain inti sikil nyuda fluks urutan nol{10}}, nambah stabilitas operasional lan nyuda geter.
Dilengkapi tank lenga baja ringan sing disegel lan radiator bergelombang sing dipasang ing mburine, nyedhiyakake pendinginan alami sing efisien (ONAN) lan linuwih -panjang. Desain ngarep sing mati-mesthekake pangopènan sing aman lan trep. Sisih dhuwur-tegangan kalebu enem bushing terisolasi 200A sing bisa dipisahake lan bushing netral H0 khusus, dene sisih voltase -rendhek nggunakake bushing jinis resin-skop-kanggo sambungan kabel sing aman. Piranti proteksi kayata sekring bayonet, -sekring pembatas saiki (CLF), lan penahan lonjakan primer nyedhiyakake isolasi kesalahan lan proteksi overvoltage sing andal.
Aplikasi umum kalebu distribusi voltase medium-nganti-sedheng ing lingkungan kutha lan pinggiran kutha kayata komunitas omah, kompleks komersial, fasilitas industri ringan, sekolah, lan rumah sakit, sing safety lan linuwih iku penting. Iki uga cocok-kanggo sistem distribusi feed loop-bawah lemah kanggo nambah linuwih pasokan.

Panas Tags: 500 kva pad dipasang trafo, pabrikan, supplier, rega, biaya
You Might Also Like
2500 kVA Tiga Phase Pad -dipasang Transformer-13.8/0...
1500 kVA Pad dipasang Transformer-34,5 / 0,48 kV|AS ...
3000 kVA Residential Transformer Box-23.9 / 11.95 * ...
1500 kVA Pad dipasang Transformer Price-23,9 / 0,416...
1000 kVA Mati Transformer ngarep-24 / 0,48 kV|AS 2024
750 kVA Pad Dipasang Transformer Biaya-13,8 / 0,22 k...
Kirim Enquiry