630 kVA Tekanan Vakum Impregnated Transformer-11 / 0,55 kV|Afrika Kidul 2025
Kapasitas: 630 kVA
Tegangan: 11/0.55 kV
Fitur: karo penggemar lan tingkat insulasi H

Distribusi Daya Cerdas, Masa Depan Ijo - Mbukak Transformers Kering Winding kanggo Kelestarian!
01 Umum
1.1 Deskripsi Proyek
630 kVA mbukak nduwurke tumpukan jinis garing trafo dikirim menyang Afrika Kidul ing 2025. Daya dirating saka mbukak nduwurke tumpukan jinis garing trafo punika 630 kVA karo AN/AF cooling, voltase utami punika 11 kV karo ± 2 * 2,5% tapping sawetara (NLTC), voltase secondary 0.55kV, padha mbentuk klompok vektor Dyn1.
Opening Winding Dry Type Transformer direkayasa kanggo kinerja sing unggul, nggabungake teknologi canggih kanthi konstruksi sing kuat kanggo nyukupi kabutuhan daya industri lan komersial. Nampilake pengontrol suhu sing cerdas, iki njamin manajemen termal sing optimal, nalika dibangun ing -kipas pendingin nambah pambuangan panas kanggo efisiensi sing konsisten sanajan ing beban sing abot.
Dirancang nganggo insulasi Kelas H, trafo iki tahan -lingkungan suhu dhuwur, ndhukung kenaikan suhu 100K kanggo operasi -panjang sing andal. Kompatibel karo sumber daya 110V, ngirim transformasi voltase stabil kanthi mundhut energi minimal.
Becik kanggo otomatisasi industri, sistem energi sing bisa dianyari, lan infrastruktur kritis, trafo tipe -kering kita nawakake operasi gratis-pangopènan, keamanan sing luwih apik (ora ana risiko kebakaran), lan kinerja sing ramah lingkungan-(ora ana emisi lenga utawa beracun). Nganyarke menyang solusi daya sing luwih cerdas lan luwih tahan banting saiki!
1.2 Spesifikasi Teknis
630 kVA VPI jinis garing trafo specifications lan data sheet
|
Dikirim menyang
Afrika Kidul
|
|
taun
2025
|
|
Jinis
Transformator tipe garing open winding
|
|
materi inti
Lembaran baja silikon berorientasi gandum
|
|
Standar
IEC60076
|
|
Daya Rated
630kVA
|
|
Frekuensi
50 HZ
|
|
Klompok vektor
Dina11
|
|
fase
3
|
|
Tipe Cooling
ONAN/ONAF
|
|
Tegangan utami
11 kV
|
|
Tegangan Sekunder
0,55 kV
|
|
Bahan Winding
alumunium
|
|
Impedansi
6%
|
|
Tutul Ganti
NLTC
|
|
Ngetuk Range
± 2*2,5%@sisih utami kanthi nutul pranala
|
|
Ora Mundhut Load
1.1KW
|
|
Ing Load Loss
8.3KW
|
|
Tingkat insulasi
H
|
1.3 Gambar
630 kVA VPI jinis garing trafo diagram drawing lan ukuran.
![]() |
![]() |
02 Produksi
2.1 Inti
Transformator tipe garing -bukaan nduweni permeabilitas dhuwur-inti laminasi baja silikon sing ngalami perawatan anil kanthi presisi kanggo nyuda kerugian sirkuit magnetik. Inti nganggo struktur stacking stepped kanggo nyuda kerugian arus eddy kanthi efektif, digabungake karo teknologi clamping khusus kanggo njamin operasi sing sepi, tanpa gangguan -.

2.2 Penggulungan

Transformator nduweni presisi-kabel aluminium tatu kanthi insulasi SHS (Super Heat-resistant Synthetic) multi-lapisan, bisa nahan suhu nganti 220 derajat . Desain ventilasi terbuka-yang inovatif njamin pambuangan panas sing optimal nalika njaga kinerja termal Kelas H (munggah suhu 100K). Struktur nduwurke tumpukan nggabungake stabilitas mekanik sing dikuatake kanthi kekuatan dielektrik sing apik banget, menehi resistensi sing unggul kanggo kejut termal, geter lan discharge parsial.
2.3 Rapat pungkasan
1) Precision mounting of SHS-insulated coils onto CRGO cores; 2) Stepped-lamination upper yoke installation with 15-20kN/m clamping force; 3) install cooling fans and PT100 smart temperature controller (150℃ alarm/180℃ trip); 4) install terminal connections passing 5000V insulation tests (>1000MΩ).

03 Testing
|
Ora. |
Item Tes |
Unit |
Nilai Penerimaan |
Nilai sing diukur |
Kesimpulan |
|
|
1 |
Pengukuran resistance winding |
/ |
Tingkat unbalance resistance maksimum Rintangan garis: Kurang saka utawa padha karo 2% |
HV (line) |
LV (garis) |
Lulus |
|
0.29% |
0.84% |
|||||
|
2 |
Pangukuran rasio voltase lan mriksa pamindahan phase |
/ |
Toleransi rasio voltase ing tapping utama: ± 1/10 Simbol sambungan: Dyn11 |
-0.02% ~ 0.13% Dina11 |
Lulus |
|
|
3 |
Pangukuran Impedansi sirkuit Short- lan Mundhut Beban |
/ kW kW |
t:145 derajat Z%: nilai sing diukur Pk: nilai sing diukur Pt: nilai diukur |
6.22% 4.745 6.485 |
Lulus |
|
|
4 |
Pangukuran Ora ana-mundhut lan Arus ing 90% lan 110% voltase dirating |
/ kW |
I0 :: nyedhiyakake nilai sing diukur P0: nyedhiyakake nilai sing diukur |
90% ur |
0.36 0.978 |
Lulus |
|
100% Ur |
0.40 1.087 |
|||||
|
110% Ur |
0.44 1.195 |
|||||
|
5 |
Tes Tegangan Terapan |
/ |
HV: 35kV 60s LV: 3kV 60s |
Ora ana ambruk voltase test |
Lulus |
|
|
6 |
Tes Induksi Tegangan Tahan |
/ |
Tegangan sing ditrapake (kV): 2 Ur Tegangan induksi (kV): 1.1 Duration(s):40 Frekuensi (HZ): 150 |
Ora ana ambruk voltase test |
Lulus |
|
|
7 |
Test discharge parsial |
pC |
Tingkat maksimal discharge parsial yaiku 10 pC |
<10 |
Lulus |
|


04 Pengepakan lan Pengiriman
4.1 Pengemasan
Transformer -jinis garing dikemas ing peti kayu sing kuat kanthi bantalan njero kanggo transportasi sing aman. Kabeh komponen, kalebu pengontrol suhu lan penggemar, wis-dipasang minangka unit lengkap. Eksterior ditandhani kanthi cetha kanthi instruksi penanganan, nyedhiyakake kelembapan sing dipercaya lan proteksi kejut kanggo pengiriman trafo jarak adoh-.

4.2 Pangiriman

Transformator tipe kering gulung bukaan bakal dikirim CIF Durban Port ing kejut -krat kayu bukti. Rega kalebu asuransi laut lan bea cukai ekspor, dene formalitas impor bakal ditangani dening panrima. Kintunan njaga asor/suhu kontrol sing ketat miturut standar anti-anti korosi internasional kanggo angkutan laut.
05 Situs lan Ringkesan
Minangka solusi efisiensi- dhuwur kanggo transmisi lan distribusi daya, Opening Winding Dry Type Transformer menehi keandalan kanggo sektor industri, energi, lan infrastruktur liwat desain-terbuka sing inovatif, manajemen termal sing unggul, lan insulasi sing kuat. Nggabungake operasi gratis-pangopènan, konstruksi-ramah lingkungan, lan kontrol suhu sing cerdas, iku unggul ing aplikasi sing nuntut nalika ndhukung tujuan energi lestari. Mitra karo kita kanggo solusi daya tepercaya-ing ngendi teknologi nyukupi safety lan efisiensi, nguatake pangiriman energi sing luwih cerdas.

Panas Tags: tekanan vakum trafo impregnated, produsen, supplier, rega, biaya
You Might Also Like
500 kVA Pad Gunung Transformer-13,8 / 0,48 kV|USA 2025
630 kVA Tipe Kering Step Down Transformer-11 / 0,55 ...
630 kVA Garing Tipe Power Transformer-11 / 0,55 kV|A...
1000 kVA Vpi Transformer-11 / 0,55 kV|Afrika Kidul 2024
630 kVA Umum Listrik Tipe Kering Transformers-11 / 0...
630 kVA Tipe Transformator Vpi-11 / 0,55 kV|Afrika K...
Kirim Enquiry